Dynamic Congestion Manager for Loads (DCMl)
Overview
Dynamic Contingency Manager for Datacenters/Loads (DCML) is Splight’s real-time grid protection solution that safeguards the transmission system by disconnecting critical datacenter loads during thermal contingencies. When a monitored transmission line or transformer experiences a breaker trip or overload condition, DCML immediately triggers a fast disconnection command to selected datacenters—causing them to switch to backup power and relieve stress on the grid.
This approach enables grid operators to operate closer to true physical capacity while still maintaining safety and reliability. DCML is designed for hyperscalers, colocation providers, and infrastructure operators participating in contingency support programs or grid reliability services.
Required Inputs
DCML depends on high-quality real-time telemetry to detect contingencies and execute fast, auditable disconnection commands. Input signals are streamed through Splight connectors using supported protocols.
Real-Time Input Attributes
For Each Datacenter (or big load):
power_draw
Real-time power consumption
Yes
At least every 5 seconds
MQTT, Modbus, DNP3, IEC81850
breaker_status
Internal breaker state (optional)
Optional
On change
MQTT, Modbus, DNP3, IEC81850
grid_connection_status
Whether the datacenter is grid-connected or on backup
Yes
At least every 5 seconds
MQTT, Modbus, DNP3, IEC81850
For Each Transmission Line:
active_power_start
Active power flow at the start node of the line (in MW)
Yes
At least every 1 second
MQTT, Modbus, DNP3
active_power_end
Active power flow at the end node of the line (in MW)
Yes
At least every 1 second
MQTT, Modbus, DNP3
breaker_status
Line breaker status: open or closed
Yes
On change
MQTT, Modbus, DNP3
current_r_start
Phase R current at the start node (RMS, in A)
Yes
At least every 1 second
MQTT, Modbus, DNP3
current_r_end
Phase R current at the end node (RMS, in A)
Yes
At least every 1 second
MQTT, Modbus, DNP3
current_s_start
Phase S current at the start node (RMS, in A)
Yes
At least every 1 second
MQTT, Modbus, DNP3
current_s_end
Phase S current at the end node (RMS, in A)
Yes
At least every 1 second
MQTT, Modbus, DNP3
current_t_start
Phase T current at the start node (RMS, in A)
Yes
At least every 1 second
MQTT, Modbus, DNP3
current_t_end
Phase T current at the end node (RMS, in A)
Yes
At least every 1 second
MQTT, Modbus, DNP3
frequency
System frequency measured at either start or end of the line (in Hz)
Yes
At least every 1 second
MQTT, Modbus, DNP3
reactive_power_start
Reactive power flow at the start node of the line (in MVAR)
Yes
At least every 1 second
MQTT, Modbus, DNP3
reactive_power_end
Reactive power flow at the end node of the line (in MVAR)
Yes
At least every 1 second
MQTT, Modbus, DNP3
switch_status_start
Disconnector or switch status at the start node (open/closed)
Yes
On change
MQTT, Modbus, DNP3
switch_status_end
Disconnector or switch status at the end node (open/closed)
Yes
On change
MQTT, Modbus, DNP3
voltage_start
Line-to-neutral voltage at the start node (RMS, in kV)
Yes
At least every 1 second
MQTT, Modbus, DNP3
voltage_end
Line-to-neutral voltage at the end node (RMS, in kV)
Yes
At least every 1 second
MQTT, Modbus, DNP3
Metadata Requirements
For each Generator:
max_capacity
Generator nameplate capacity
Yes
100 MW
For the Grid:
maximum_allowed_diconnection
Provided by the electrical study performed by Splight
Yes
303MW
Note: Telemetry must have timestamps aligned to UTC ±30s. Poor quality input may block control actions and disable contingency response.
Features
DCML includes a fixed set of analytics and visualizations designed to give visibility into contingency readiness and actual response behavior.
Datacenter Power Draw (Real-Time)
Current load per datacenter
MW
Historical Power Draw
Time-series of datacenter consumption
MW over time
Line Loading
Current and historical loading of monitored lines
% or MW
Total Grid Offload via DCML
Sum of load shed through DCM actions
MW
Disconnection Matrix
Real-time contingency map: which datacenters will disconnect under which failures
Boolean matrix
Control Capabilities
DCML issues disconnection commands to participating datacenters when a contingency is detected. These are enforced via connector-based setpoints or breaker interface.
Control Logic Summary
System continuously monitors breaker line loadings and statuses
If a contingency is detected, the Disconnection Matrix determines which datacenters must switch to backup
Command is sent to disconnect from grid immediately
Commands Issued
disconnect
Triggered via asset control attribute
Breaks physical tie to grid
Timing and Safety
Total response time: < 500 ms from event detection to command dispatch
Each control action is logged with timestamp and associated contingency
Disconnections are only sent when DCML detects a real contingency event
Deployment Notes
DCML requires a pre-modeled Equivalent Grid using Splight's SLD tooling, based on prior engineering studies
Each datacenter and transmission line must be onboarded as an asset with complete metadata and real-time input streams
Only Splight-controlled connectors can issue control commands (self-hosted nodes must meet latency guarantees)
Support
Need help validating inputs, testing control logic, or scaling up? Contact your Implementation Manager or email [email protected].
Watch this video walkthrough
Video comming soon
Last updated
Was this helpful?